Class 1 Div 1 certified Intrinsically Safe true wireless system powers HART, 4-20mA, 1-5V and DI sensors from internal battery with 1 mile range.
| 
 Operating Temp  | 
 -40C to 60C  | 
| 
 Humidity  | 
 0% - 100% Condensing  | 
| 
 Power  | 
 3 X D LithiumBatteryPack. Field Replaceable. Class 1, Division 1 Certified when used with SignalFire System. In Situ replacement does not require a work ticket.  | 
| 
 Sensor Power  | 
 18V for 4-20 mA CurrentLoopor Hart Sensors. Sensor power is provided from the system, no need for external sensor power, no barriers required if used in compliance with control drawings.  | 
| 
 BatteryLife  | 
 1-4 years depending on the number and type of sensors and reporting frequency  | 
| 
 Data Interface  | 
 Wireless – Available as Modbus Registers at Gateway  | 
| 
 Supported Sensor Interfaces  | 
 Hart (up to 4 devices), 4-20 mA Current Loop, 1-5 Volt, Digital Input (State, Counter ,Totals, Frequency), Digital Output (TTL Level)  | 
| 
 Display  | 
 Externally visible display shows communications status and sensor readings  | 
| 
 Data Update Rates  | 
 User Selectable Rotary Switch from 5 sec to 2 hours  | 
| 
 Radio Power  | 
 10 mW  | 
| 
 Antenna Type  | 
 External Weather Resistant, Omnidirectional  | 
| 
 Antenna Gain  | 
 5dB  | 
| 
 Receive Sensitivity  | 
 -105 dB  | 
| 
 Frequency  | 
 902-928 MHz, FHSS, License Free ISM Band Compliant with FCC Part 15  | 
| 
 Range  | 
 1+ Mile (Line of Sight, Real World)  | 
| 
 Networks  | 
 Up to 64 separate networks. Rotary Switch Selectable  | 
| 
 Enclosure  | 
 Fiberglass Reinforced UV Stabilized Plastic  | 
| 
 Intrinsically Safe  | 
 Class 1, Division 1, Temp Code T3, Groups C&D. Conforms to UL Std. 913, Certified to Can/CSA Std C22.2 No. 157  | 
| 
 Internal Diagnostics  | 
 Battery Voltage, Signal Strength, Error Conditions  | 
Greentech » Environmental Monitoring
Industrial Applications » Tank Monitoring
Industrial Applications » Irrigation
Industrial Applications » Process Control, SCADA
Interface » Type of Inputs / Outputs » Analog
Interface » Type of Inputs / Outputs » Digital
Environment » Temperature Range » Industrial (-25°C / +65°C)
Power Supply » Battery » Operation / Standby Time